Clbm1dphu-400 1500V, 250/350/ 400A Molded Case Circuit Breaker MCCB

1500V, 250/350/400A Moulded Case Circuit Breaker MCCBDC system-specific circuit breakers are used in rated insulation voltage of 1600V and a rated operating voltage of DC1500V and below, and rated operating currents of 250A and below. C ircuit breakers are mainly used for overload and short circuit protection of distributed powe

Featured Products

1500V, 250/350/400A Moulded Case Circuit Breaker MCCB


Clbm1dphu-400 1500V, 250/350/400A Moulded Case Circuit Breaker MCCBClbm1dphu-400 1500V, 250/350/400A Moulded Case Circuit Breaker MCCBClbm1dphu-400 1500V, 250/350/400A Moulded Case Circuit Breaker MCCBClbm1dphu-400 1500V, 250/350/400A Moulded Case Circuit Breaker MCCBClbm1dphu-400 1500V, 250/350/400A Moulded Case Circuit Breaker MCCB

DC system-specific circuit breakers are used in rated insulation voltage of 1600V and a rated operating voltage of DC1500V and below, and rated operating currents of 250A and below. C ircuit breakers are mainly used for overload and short circuit protection of distributed power and protection circuits and power equipment in DC systems . U nder normal circumstances can be used as a line of infrequent conversion and DC motor infrequent start.

1.Normal conditions of use

Ambient air temperature does not exceed the upper limit of +70ºC, the lower limit of not less than -40ºC , 24-hour average does not exceed +35ºC. (Note: Circuit breakers for use in ambient air temperatures above + 70ºC or below -40ºC should be consulted with the manufacturer);
The installation site of the altitude does not exceed 2000m (2000m above the need for the corresponding derating)
The relative temperature of the atmosphere is not more than 50% at the highest temperature around +40ºC, and can be compared at a lower temperature.High relative humidity (for example, 90% at 20ºC), and the consideration of temperature change on the surface of the product dew.
2.Normal installation conditions
Installation conditions: the general should be vertical installation or horizontal installation;
Installation categories: Class III of circuit breaker main circuit, control circuit and auxiliary circuit are class II.
Pollution level: Three
3.Normal storage and transport conditions
The temperature limit is not lower than -40ºC,the upper limit does not exceed +70ºC Relative humidity (25ºC) does not exceed 95ºC;
The product should be lightly moved during transport,should not be reversed should be acoided violent collision Main technical parameters

Main technical parameters 

Frame level250ARated working voltageDC500V/DC1000V DC1250V/DC1500V
Rated working current(A)100/125/140/160
/180/200/225/250
Rated insulation voltageDC160
Pole number2Arcing distance≤50mm
Breaking capacityIcu=Ics=15kAMechanical life200
Short circuit 
instantaneous setting
5~10Degree of protectionIp20
Standard ruleGB14048.2 IEC60947

Description of protection

Overload long delay protection

Ambient temperatureTest currentAppointment timeStarting state
+50ºC±2ºC1.05In≥No actionCold state
1.3In<2h actionHot state

Short-circuit transient protection

Ambient temperatureTest currentAppointment timeStarting state

+10ºC~+40ºC

4In or 8In≥200msNo action
6In or 12In<200msaction

Derated coefficient when ambient temperature changes

Ambient temperature40ºC45ºC50ºC55ºC60ºC65ºC
Derated coefficient1In0.97In0.93In0.89In0.85In0.82In

A comparative relationship between the rated current of a circuit breaker and the cross section of a linked wire

Rated current100A125A140A160A180A200A225A250A
Cable intercepting area35mm²50mm²70mm²95mm²120mm²

.High altitude derated coefficient

Altitude2000m3000m4000m5000m
Operating voltage derating coefficient10.90.80.7
Operating current derating coefficient10.960.930.9